image Resources and Function Sets


Line 410 – Table 7


Function Set

Utility Server

Aggregator

DER Client

Time

MUST

MUST

MUST

Device

Capability

MUST

MUST

MUST

End Device

MUST

MUST

MUST

FSA

MUST

MUST

MUST

DER

MUST

MUST

MUST

Response

MAY

MUST

MUST

Meter/Mirror

Meter

MAY

MUST

MUST

Log Event

MAY

MAY

MAY


Subscription/N

otification

MUST

MUST

MAY

Security

MUST

MUST

MUST


image Commissioning and Identification of DER Requirements


Lines 555-565

In the Aggregator scenario, the DERs under the management of the Aggregator may not be IEEE 2030.5 devices – that is, they may not have a device certificate. In this case, the Aggregator will produce the LFDI (see section 5.2.1.2). In all cases, this identity and the associated LFDI are returned to the Aggregator for their uses in ensuring communications are routed correctly.

In the rare event that an LFDI collision is detected (i.e. two unique certificates or IDs hash to the same LFDI value), the certificates or IDs of the offending DERs will need to be replaced or re-generated. This may require returning the DERs to the manufacturer for certificate replacement. Note that the probability of a LFDI collision is infinitesimally small. It is much more likely the collision was caused by an accidental duplication of the certificate or ID.


image DER Controls and DER Default Control Requirements


Line 601 – Table 9


Grid DER Support Functions

IEEE 2030.5 DERControls

IEEE 2030.5 DefaultDERControls

Ramp Rate Setting


setGradW


setSoftGradW

Connect/Disconnect

opModEnergize

opModEnergize

Real Power Output Limit

Control

opModMaxLimW

opModMaxLimW

Site Export Limit (in Watts)

opModExpLimW

opModExpLimW

Site Import Limit (in Watts)

opModImpLimW

opModImpLimW

Max generation limit

opModGenLimW

opModGenLimW

Max load limit

opModLoadLimW

opModLoadLimW


Refer to Annex B for further specification of the four DER management envelope extensions.


Lines 602-604

The Ramp Rate Setting function is used to control the ramp rate of the DefaultDERControl controls and is used to manage the rate of application of the failsafe controls.

The DER Client will need to store the DefaultDERControl settings between communication and electrical network interruptions.

5.2.4.1 Scheduling of Controls


Lines 606-607

DERControls are IEEE 2030.5 events and SHALL conform to all the event rules in Section 10.2.3 of IEEE 2030.5-2018.


5.2.5.1 Monitor Data


Lines 651-652 Tables 10 – 11

Refer to Annex A for details on expected monitoring data, attributes and data qualifiers.